Description
Generac XG04045CNAC Overview
The Generac XG04045CNAC is the CARB version of a liquid-cooled, three-phase automatic standby generator. A 4.5-liter inline four-cylinder engine turning at 1,800 RPM drives the alternator, and a Power Zone 410 controller manages the whole unit. That controller is NFPA 110 capable.
Fuel is chosen at the controller, natural gas or propane vapor, so one cabinet covers either supply. Output is 208/120 V three-phase, and the generator can be reconfigured for 480/277 V or 240/120 V with an optional field-installable VCC. The enclosure and frame resist corrosion, and the unit can be placed as close as 18 in (457 mm) from a structure. Cellular connectivity ties the generator into Mobile Link and Fleet, and the design is described as quiet in operation. A 5-year/2,000-hour limited warranty is listed for the unit.
Key Features
- A Power Zone 410 controller, which is NFPA 110 capable, manages the generator and handles fuel selection
- Built-in cellular connectivity links the unit to Mobile Link and Fleet for remote monitoring
- Fuel type is selected at the controller, so the same unit can run on natural gas or propane vapor
- High motor-starting ability and surge capacity help it cope with loads that draw heavily when they start
- The corrosion-resistant enclosure and frame come with quiet operation, and the unit can sit as close as 18 in (457 mm) to a structure
- Routine maintenance is handled from one side of the unit, so servicing needs access to only a single side
- EPA and SCAQMD exhaust emissions certification, together with a 5-year/2,000-hour limited warranty
Who It’s For
A fit for buyers who need automatic three-phase standby power and want a controller that reports over a cellular link. As the CARB version, it is the variant to look at when that designation matters, and the selectable fuel type helps wherever natural gas or propane vapor is on hand.
Specifications
| SKU | XG04045CNAC | |||||||
| Brand | Generac | |||||||
| Generator Output | ||||||||
| Voltage | XG03245 | XG04045 | ||||||
| Natural Gas | Liquid Propane | |||||||
| Power (kW) | Current (A) | Power (kW) | Current (A) | |||||
| 120/240 1-Phase | 32 | 133 | 32 | 133 | 40 | 40 | 139 | |
| 208/120 3-Phase | 32 | 111 | 32 | 111 | 40 | 40 | 120 | |
| 240/120 3-Phase | 32 | 32 | 40 | 40 | ||||
| 480/277 3-Phase | 32 | 32 | 40 | 40 | ||||
| Voltage Regulation | ||||||||
| Type | Electronic | |||||||
| Sensing | All Phases | |||||||
| Regulation | +- 1 percent | |||||||
| Governor Specifications | ||||||||
| Type | Electronic | |||||||
| Frequency Regulation | Isochronous | |||||||
| Steady State Regulation | +- 25 percent | |||||||
| Alternator System Specifications | ||||||||
| XG03245 | XG04045 | |||||||
| 1-Phase | 3-Phase | 1-Phase | 3-Phase | |||||
| Voltage Output | 120/240 V Only | 208/120 V; Configurable for 480/277 or 240/120 V with Optional Field-Installable VCC | 120/240 V Only | 208/120 V; Configurable for 480/277 or 240/120 V with Optional Field-Installable VCC | ||||
| Circuit Breaker (CB) Size | 150 A | Not Included; Optional Field-Installable Kit | 200 A | Not Included; Optional Field-Installable Kit | ||||
| Type | Synchronous | Synchronous | ||||||
| Rotor Insulation Class | F | F | ||||||
| Stator Insulation Class | H | H | ||||||
| Telephone Interference Factor (TIF) | < 50 | < 50 | ||||||
| Bearings | Sealed Ball | Sealed Ball | ||||||
| Coupling | Flexible Disc | Flexible Disc | ||||||
| Excitation System | Direct | Direct | ||||||
| Engine Specifications | ||||||||
| XG03245 | XG04045 | |||||||
| Make | Generac | |||||||
| Model | Inline 4 Cylinder | |||||||
| Cylinders | 4 | |||||||
| Displacement (L) | 4.5 | |||||||
| Bore | 4.5 in | |||||||
| Stroke | 4.25 in | |||||||
| Compression Ratio | 9.9:1 | |||||||
| Lifter Type | Hydraulic | |||||||
| Intake Air System | Naturally Aspirated | |||||||
| Temperature Derate | 1.5% per every 5°C above 25°C (1.65% per every 10°F above 77°F) | |||||||
| Altitude Derate | 1% per every 100 m above 183 m (3% per every 1000 ft above 600 ft) | |||||||
| Exercise Speed (RPM) | 1,200 | |||||||
| Operating Speed (RPM) | 1,800 | |||||||
| Cooling System | ||||||||
| XG03245 | XG04045 | |||||||
| Coolant | 50/50 (50% Ethylene Glycol) | |||||||
| Coolant System Capacity (L (US gal)) | 11 (2.9) | |||||||
| Water Pump | Belt-Driven | |||||||
| Fan Type | Mechanical | |||||||
| Fan Quantity | 1 | |||||||
| Maximum Ambient Air Temperature (C (F)) | 50 (122) | |||||||
| Fuel Types | ||||||||
| XG03245 | XG04045 | |||||||
| Natural Gas | Yes | |||||||
| NG Pressure (kPa (in. WC)) | 0.87: 3.48 (3.5-14) | |||||||
| Liquid Propane | Yes | |||||||
| LP Vapor Pressue (kPa (in. WC)) | 1.74: 3.48 (7-14) | |||||||
| Fuel Type Configuration | Controller-Selected | |||||||
| Fuel Shutoff Solenoid | Standard, Dual | |||||||
| Fuel Consumption | ||||||||
| Rated Load | XG03245 | XG04045 | ||||||
| Natural Gas | Liquid Propane | Natural Gas | Liquid Propane | |||||
| (m3/h) | (CFH) | (m3/h) | (CFH) | (m3/h) | (CFH) | (m3/h) | (CFH) | |
| 25% | 4.8 | 169 | 8.3 | 2.2 | 5.2 | 184 | 10 | 2.6 |
| 50% | 6.8 | 240 | 12.9 | 3.4 | 8.2 | 289 | 14.5 | 3.8 |
| 75% | 9.5 | 335 | 15.8 | 4.2 | 11.1 | 392 | 17.7 | 4.7 |
| 100% | 11.5 | 406 | 18.5 | 4.9 | 14 | 494 | 21.7 | 5.7 |
| Electrical System | ||||||||
| System Voltage | 12 | |||||||
| Battery Charge Alternator (A) | 37 | |||||||
| Battery Charger (A) | 5 | |||||||
| Recommended Battery (not included) | Group 27R, 725 CCA Minimum | |||||||
| Maximum Allowable Battery | Group 31R | |||||||
Frequently asked questions
What does the CARB designation mean for the Generac XG04045CNAC?
The listing describes the XG04045CNAC as the CARB version of Generac’s liquid-cooled, three-phase automatic standby generator, and says it is the variant to look at when that designation matters. It also lists EPA and SCAQMD exhaust emissions certification for the unit.
What fuel does the XG04045CNAC run on?
Fuel type is selected at the Power Zone 410 controller, so the same cabinet runs on natural gas or propane vapor. The listing gives a natural gas supply pressure of 3.5 to 14 in. WC and an LP vapor pressure of 7 to 14 in. WC, with a dual fuel shutoff solenoid as standard.
What voltage does the Generac XG04045CNAC put out?
Output is 208/120 V three-phase. The generator can be reconfigured for 480/277 V or 240/120 V with an optional field-installable VCC. Voltage regulation uses electronic sensing on all phases, listed at plus or minus 1 percent, and the engine runs at 1,800 RPM with a 1,200 RPM exercise speed.
How is the XG04045CNAC monitored remotely?
Built-in cellular connectivity links the generator to Mobile Link and Fleet for remote monitoring. The Power Zone 410 controller, which is NFPA 110 capable, manages the whole unit and also handles fuel selection, so status and settings run through one controller.
How close to a building can it be installed, and how is it serviced?
The listing says the unit can sit as close as 18 in (457 mm) to a structure. Its enclosure and frame resist corrosion, and routine maintenance is handled from one side of the unit, so servicing needs access to only a single side.
What battery does the Generac XG04045CNAC need?
The recommended battery is not included. The listing calls for a Group 27R battery with 725 CCA minimum, and Group 31R is the maximum allowable size. The electrical system runs at 12 volts, with a 37 A battery charge alternator and a 5 A battery charger.
Buying advice: read our guide to whole house generator cost, or compare all home standby generators.


Reviews
There are no reviews yet.