Description
Generac XG03245ANAX 32kW LC Single Phase Standby Generator Overview
The Generac XG03245ANAX is a 32kW LC automatic standby generator in single-phase form. It runs on natural gas or propane vapor, with the fuel type selected through the controller, and it is certified for EPA and SCAQMD exhaust emissions.
A Power Zone 410 controller that is NFPA 110 capable manages the system, and cellular connectivity supports Mobile Link and Fleet monitoring. The single-phase alternator delivers 120/240V and is fitted with a 150 A circuit breaker. Under the enclosure is an inline 4-cylinder, 4.5 L Generac engine with hydraulic lifters and natural aspiration, running at 1,800 RPM and exercising at 1,200 RPM. It is cooled by a 50/50 ethylene glycol mix (2.9 US gallons of coolant capacity), and an electronic governor and electronic voltage regulation hold output to within 1 percent. The 12V system includes a 5 A battery charger and a 37 A charging alternator; a Group 27R battery is recommended but not included. At full load the 32kW model draws 406 cubic feet per hour of natural gas, and output derates 1.5 percent for every 5 degrees C above 25 degrees C. The alternator is a synchronous design with sealed ball bearings, rotor insulation is class F and stator insulation is class H, and the carton includes the generator and an owner’s manual.
Key Features
- Power Zone 410 controller, NFPA 110 capable
- Cellular connectivity for Mobile Link and Fleet
- Controller-selectable fuel: natural gas or propane vapor
- High motor starting and surge capacity
- Corrosion-resistant enclosure and frame
- Single-side access for regular maintenance
- Can sit as close as 18 inches (457 mm) from a structure
Who It’s For
This generator is for commercial and larger residential sites that want automatic standby power on single-phase service. A 5-year limited factory warranty (2,000 hour) is listed.
Specifications
| SKU | XG03245ANAX | |||||||
| Brand | Generac | |||||||
| Generator Output | ||||||||
| Voltage | XG03245 | XG04045 | ||||||
| Natural Gas | Liquid Propane | |||||||
| Power (kW) | Current (A) | Power (kW) | Current (A) | |||||
| 120/240 1-Phase | 32 | 133 | 32 | 133 | 40 | 40 | 139 | |
| 208/120 3-Phase | 32 | 111 | 32 | 111 | 40 | 40 | 120 | |
| 240/120 3-Phase | 32 | 32 | 40 | 40 | ||||
| 480/277 3-Phase | 32 | 32 | 40 | 40 | ||||
| Voltage Regulation | ||||||||
| Type | Electronic | |||||||
| Sensing | All Phases | |||||||
| Regulation | +- 1 percent | |||||||
| Governor Specifications | ||||||||
| Type | Electronic | |||||||
| Frequency Regulation | Isochronous | |||||||
| Steady State Regulation | +- 25 percent | |||||||
| Alternator System Specifications | ||||||||
| XG03245 | XG04045 | |||||||
| 1-Phase | 3-Phase | 1-Phase | 3-Phase | |||||
| Voltage Output | 120/240 V Only | 208/120 V; Configurable for 480/277 or 240/120 V with Optional Field-Installable VCC | 120/240 V Only | 208/120 V; Configurable for 480/277 or 240/120 V with Optional Field-Installable VCC | ||||
| Circuit Breaker (CB) Size | 150 A | Not Included; Optional Field-Installable Kit | 200 A | Not Included; Optional Field-Installable Kit | ||||
| Type | Synchronous | Synchronous | ||||||
| Rotor Insulation Class | F | F | ||||||
| Stator Insulation Class | H | H | ||||||
| Telephone Interference Factor (TIF) | < 50 | < 50 | ||||||
| Bearings | Sealed Ball | Sealed Ball | ||||||
| Coupling | Flexible Disc | Flexible Disc | ||||||
| Excitation System | Direct | Direct | ||||||
| Engine Specifications | ||||||||
| XG03245 | XG04045 | |||||||
| Make | Generac | |||||||
| Model | Inline 4 Cylinder | |||||||
| Cylinders | 4 | |||||||
| Displacement (L) | 4.5 | |||||||
| Bore | 4.5 in | |||||||
| Stroke | 4.25 in | |||||||
| Compression Ratio | 9.9:1 | |||||||
| Lifter Type | Hydraulic | |||||||
| Intake Air System | Naturally Aspirated | |||||||
| Temperature Derate | 1.5% per every 5°C above 25°C (1.65% per every 10°F above 77°F) | |||||||
| Altitude Derate | 1% per every 100 m above 183 m (3% per every 1000 ft above 600 ft) | |||||||
| Exercise Speed (RPM) | 1,200 | |||||||
| Operating Speed (RPM) | 1,800 | |||||||
| Cooling System | ||||||||
| XG03245 | XG04045 | |||||||
| Coolant | 50/50 (50% Ethylene Glycol) | |||||||
| Coolant System Capacity (L (US gal)) | 11 (2.9) | |||||||
| Water Pump | Belt-Driven | |||||||
| Fan Type | Mechanical | |||||||
| Fan Quantity | 1 | |||||||
| Maximum Ambient Air Temperature (C (F)) | 50 (122) | |||||||
| Fuel Types | ||||||||
| XG03245 | XG04045 | |||||||
| Natural Gas | Yes | |||||||
| NG Pressure (kPa (in. WC)) | 0.87: 3.48 (3.5-14) | |||||||
| Liquid Propane | Yes | |||||||
| LP Vapor Pressue (kPa (in. WC)) | 1.74: 3.48 (7-14) | |||||||
| Fuel Type Configuration | Controller-Selected | |||||||
| Fuel Shutoff Solenoid | Standard, Dual | |||||||
| Fuel Consumption | ||||||||
| Rated Load | XG03245 | XG04045 | ||||||
| Natural Gas | Liquid Propane | Natural Gas | Liquid Propane | |||||
| (m3/h) | (CFH) | (m3/h) | (CFH) | (m3/h) | (CFH) | (m3/h) | (CFH) | |
| 25% | 4.8 | 169 | 8.3 | 2.2 | 5.2 | 184 | 10 | 2.6 |
| 50% | 6.8 | 240 | 12.9 | 3.4 | 8.2 | 289 | 14.5 | 3.8 |
| 75% | 9.5 | 335 | 15.8 | 4.2 | 11.1 | 392 | 17.7 | 4.7 |
| 100% | 11.5 | 406 | 18.5 | 4.9 | 14 | 494 | 21.7 | 5.7 |
| Electrical System | ||||||||
| System Voltage | 12 | |||||||
| Battery Charge Alternator (A) | 37 | |||||||
| Battery Charger (A) | 5 | |||||||
| Recommended Battery (not included) | Group 27R, 725 CCA Minimum | |||||||
| Maximum Allowable Battery | Group 31R | |||||||
Frequently asked questions
What fuel does the Generac XG03245ANAX run on?
It runs on natural gas or propane vapor, with the fuel type selected through the controller. At full load it draws 406 cubic feet per hour of natural gas, and it is certified for EPA and SCAQMD exhaust emissions.
What controller does the XG03245ANAX use?
A Power Zone 410 controller that is NFPA 110 capable manages the system and selects the fuel type. Cellular connectivity supports Mobile Link and Fleet monitoring of the generator.
What is the output of the Generac XG03245ANAX?
The single-phase alternator delivers 120/240V and is fitted with a 150 A circuit breaker. Electronic voltage regulation holds output to within 1 percent, and the alternator is a synchronous design with sealed ball bearings.
What engine does the XG03245ANAX have?
An inline 4-cylinder, 4.5 L Generac engine with hydraulic lifters and natural aspiration, running at 1,800 RPM and exercising at 1,200 RPM. It is cooled by a 50/50 ethylene glycol mix with 2.9 US gallons of coolant capacity.
Is a battery included with the Generac XG03245ANAX?
No. A Group 27R battery is recommended but not included. The 12V system has a 5 A battery charger and a 37 A charging alternator.
How close to a building can the XG03245ANAX sit?
It can sit as close as 18 inches (457 mm) from a structure. Output derates 1.5 percent for every 5 degrees C above 25 degrees C, and single-side access simplifies regular maintenance.
Buying advice: read our guide to whole house generator cost, or compare all home standby generators.


Reviews
There are no reviews yet.