Description
Generac XG04045ANAX 45kW LC Single Phase Standby Generator Overview
The Generac XG04045ANAX is a 45kW LC automatic standby generator with single-phase output. It can burn natural gas or propane vapor, selected through the controller, and its exhaust emissions are EPA and SCAQMD certified.
A Power Zone 410 controller, NFPA 110 capable, handles control duties, and cellular connectivity supports Mobile Link and Fleet. The alternator delivers 120/240V, and a 200 A circuit breaker is part of the single-phase configuration. The engine is an inline 4-cylinder Generac design displacing 4.5 L, with hydraulic lifters, natural aspiration and a 1,800 RPM operating speed. It is liquid cooled with a 50/50 ethylene glycol mix, and voltage is regulated electronically to within 1 percent. The electrical system is 12V with a 5 A charger and a 37 A charging alternator, and a Group 27R battery with at least 725 CCA is recommended but not included. Full-load natural gas consumption is listed at 494 cubic feet per hour for the 45kW size, and the rated ambient limit is 50 degrees C (122 degrees F). The alternator is a synchronous design with sealed ball bearings, rotor insulation is class F and stator insulation is class H, and the carton includes the generator and an owner’s manual.
Key Features
- Single-phase 120/240V output at 45kW
- Power Zone 410 controller, NFPA 110 capable
- Cellular connectivity for Mobile Link and Fleet
- Controller-selectable natural gas or propane vapor
- Fuel efficiency, high motor starting and surge capacity
- Quiet operation in a corrosion-resistant enclosure and frame
- Placement as close as 18 inches (457 mm) from a structure
Who It’s For
This model is for larger homes, commercial properties and other sites that want 45kW of automatic standby power on a single-phase supply. A 5-year limited factory warranty comes with it.
Specifications
| SKU | XG04045ANAX | |||||||
| Brand | Generac | |||||||
| Generator Output | ||||||||
| Voltage | XG03245 | XG04045 | ||||||
| Natural Gas | Liquid Propane | |||||||
| Power (kW) | Current (A) | Power (kW) | Current (A) | |||||
| 120/240 1-Phase | 32 | 133 | 32 | 133 | 40 | 40 | 139 | |
| 208/120 3-Phase | 32 | 111 | 32 | 111 | 40 | 40 | 120 | |
| 240/120 3-Phase | 32 | 32 | 40 | 40 | ||||
| 480/277 3-Phase | 32 | 32 | 40 | 40 | ||||
| Voltage Regulation | ||||||||
| Type | Electronic | |||||||
| Sensing | All Phases | |||||||
| Regulation | +- 1 percent | |||||||
| Governor Specifications | ||||||||
| Type | Electronic | |||||||
| Frequency Regulation | Isochronous | |||||||
| Steady State Regulation | +- 25 percent | |||||||
| Alternator System Specifications | ||||||||
| XG03245 | XG04045 | |||||||
| 1-Phase | 3-Phase | 1-Phase | 3-Phase | |||||
| Voltage Output | 120/240 V Only | 208/120 V; Configurable for 480/277 or 240/120 V with Optional Field-Installable VCC | 120/240 V Only | 208/120 V; Configurable for 480/277 or 240/120 V with Optional Field-Installable VCC | ||||
| Circuit Breaker (CB) Size | 150 A | Not Included; Optional Field-Installable Kit | 200 A | Not Included; Optional Field-Installable Kit | ||||
| Type | Synchronous | Synchronous | ||||||
| Rotor Insulation Class | F | F | ||||||
| Stator Insulation Class | H | H | ||||||
| Telephone Interference Factor (TIF) | < 50 | < 50 | ||||||
| Bearings | Sealed Ball | Sealed Ball | ||||||
| Coupling | Flexible Disc | Flexible Disc | ||||||
| Excitation System | Direct | Direct | ||||||
| Engine Specifications | ||||||||
| XG03245 | XG04045 | |||||||
| Make | Generac | |||||||
| Model | Inline 4 Cylinder | |||||||
| Cylinders | 4 | |||||||
| Displacement (L) | 4.5 | |||||||
| Bore | 4.5 in | |||||||
| Stroke | 4.25 in | |||||||
| Compression Ratio | 9.9:1 | |||||||
| Lifter Type | Hydraulic | |||||||
| Intake Air System | Naturally Aspirated | |||||||
| Temperature Derate | 1.5% per every 5°C above 25°C (1.65% per every 10°F above 77°F) | |||||||
| Altitude Derate | 1% per every 100 m above 183 m (3% per every 1000 ft above 600 ft) | |||||||
| Exercise Speed (RPM) | 1,200 | |||||||
| Operating Speed (RPM) | 1,800 | |||||||
| Cooling System | ||||||||
| XG03245 | XG04045 | |||||||
| Coolant | 50/50 (50% Ethylene Glycol) | |||||||
| Coolant System Capacity (L (US gal)) | 11 (2.9) | |||||||
| Water Pump | Belt-Driven | |||||||
| Fan Type | Mechanical | |||||||
| Fan Quantity | 1 | |||||||
| Maximum Ambient Air Temperature (C (F)) | 50 (122) | |||||||
| Fuel Types | ||||||||
| XG03245 | XG04045 | |||||||
| Natural Gas | Yes | |||||||
| NG Pressure (kPa (in. WC)) | 0.87: 3.48 (3.5-14) | |||||||
| Liquid Propane | Yes | |||||||
| LP Vapor Pressue (kPa (in. WC)) | 1.74: 3.48 (7-14) | |||||||
| Fuel Type Configuration | Controller-Selected | |||||||
| Fuel Shutoff Solenoid | Standard, Dual | |||||||
| Fuel Consumption | ||||||||
| Rated Load | XG03245 | XG04045 | ||||||
| Natural Gas | Liquid Propane | Natural Gas | Liquid Propane | |||||
| (m3/h) | (CFH) | (m3/h) | (CFH) | (m3/h) | (CFH) | (m3/h) | (CFH) | |
| 25% | 4.8 | 169 | 8.3 | 2.2 | 5.2 | 184 | 10 | 2.6 |
| 50% | 6.8 | 240 | 12.9 | 3.4 | 8.2 | 289 | 14.5 | 3.8 |
| 75% | 9.5 | 335 | 15.8 | 4.2 | 11.1 | 392 | 17.7 | 4.7 |
| 100% | 11.5 | 406 | 18.5 | 4.9 | 14 | 494 | 21.7 | 5.7 |
| Electrical System | ||||||||
| System Voltage | 12 | |||||||
| Battery Charge Alternator (A) | 37 | |||||||
| Battery Charger (A) | 5 | |||||||
| Recommended Battery (not included) | Group 27R, 725 CCA Minimum | |||||||
| Maximum Allowable Battery | Group 31R | |||||||
Frequently asked questions
What fuel does the Generac XG04045ANAX use?
It can burn natural gas or propane vapor, selected through the controller, and its exhaust emissions are EPA and SCAQMD certified. Full-load natural gas consumption is listed at 494 cubic feet per hour.
What controller does the XG04045ANAX have?
A Power Zone 410 controller, NFPA 110 capable, handles control duties, including fuel selection, and cellular connectivity supports Mobile Link and Fleet monitoring of the generator.
What is the electrical output of the Generac XG04045ANAX?
The alternator delivers single-phase 120/240V, and a 200 A circuit breaker is part of the single-phase configuration. Voltage is regulated electronically to within 1 percent.
What engine is in the XG04045ANAX?
An inline 4-cylinder Generac design displacing 4.5 L, with hydraulic lifters, natural aspiration and a 1,800 RPM operating speed. It is liquid cooled with a 50/50 ethylene glycol mix.
Does the Generac XG04045ANAX come with a battery?
No. A Group 27R battery with at least 725 CCA is recommended but not included. The 12V electrical system has a 5 A charger and a 37 A charging alternator.
How close to a structure can the XG04045ANAX be placed?
As close as 18 inches (457 mm) from a structure. The rated ambient limit is 50 degrees C (122 degrees F), and the enclosure and frame are corrosion resistant.
Buying advice: read our guide to whole house generator cost, or compare all home standby generators.


Reviews